The relieving or retention pressure of the safety / pressure retention valve is infinitely adjustable between 2-16 bar via the pilot valve. Any excessive system pressure is relieved via the main valve opening quickly. The electric solenoid valve controls the filling and emptying of the pilot chamber. The main valve is opened at zero current and closed when energized. To avoid water hammers, the closing rate is adjustable via the throttle check valve.
Version / position of main valve:
- Closed at zero current (model no. 1403)
- Open at zero current (model no. 1404)
Use:
- Protection of a system from excess pressure (safety valve)
- Retention of preset system pressure in the upstream pipe network (pressure retention valve)
Minimum inlet pressure: 1 bar
Minimum pressure difference between inlet and outlet pressure: 1 bar
For rating, please specify the following:
- Flow (min., med., max.)
- Inlet pressure (P1 side)
- Retention pressure and/or relieving pressure (P2 side)
- Holding pressure / back pressure
- Voltage (e.g. 24 V / 230 V)
- Type of power (alternating current / direct current)
- Type 1403 or 1404
Technical datasheet